Description
Spesifikasi Schneider MCCB / Molded Case Circuit Breakers LV429540
Main
- Range : Compact
- Product name : Compact NSX
- Product or component type : Circuit breaker
- Device short name : Compact NSX100B
- Device application : Distribution
- Poles description : 3P
- Protected poles description : 2t
- Network type : AC
- Network frequency : 50/60 Hz
- [In] Rate curren : 100 A ( 40 °C )
- [Ui] Rate insulation volt : 800 V AC 50/60 Hz
- [Uimp] rated impulse withstand voltage : 8 kV
- [Ue] Rated operational volt : 690 V AC 50/60 Hz
- Breaking capacity code : B (25 kA) AC
- Breaking capacity :
25 kA Icu at : 380/415 V AC,
15 kA Icu at : 500 V AC,
20 kA Icu at : 440 V AC,
40 kA Icu at : 220 / 240 V AC, 50 / 60 Hz conform. to IEC 60947-2; - [Ics] rated service breaking capacity :
Ics 40 kA 220 / 240 V AC, 50 / 60 Hz conform. to IEC 60947-2
Ics 7.5 kA 500 V AC 50 / 60 Hz conform. to IEC 60947-2 - Suitability for isolation :
Yes conforming to EN 60947-2
Yes conforming to IEC 60947-2 - Utilisation category : Category A
- Trip unit name : TM-D
- Trip unit technology : Thermal-magnetic
- Trip unit protection functions : LI
- Trip unit rating : 100 A ( 40 Deg C )
- Protection type :
Overload protection (thermal) L
Short-circuit protection (magnetic) I
Pollution degree : 3 conforming to IEC 60664-1
Complementary
- Control type :Toggle
- Mounting mode : Fixed
- Mounting support : Backplate
- Upside connection : Front
- Downside connection : Front
Mechanical durability : 50000 cycles - Electrical durability :
10000 cycles 690 V In conform. to IEC 60947-2
20000 cycles 690 V In/2 conform. to IEC 60947-2
30000 cycles 440 V In conform. to IEC 60947-2
50000 cycles 440 V In/2 conform. to IEC 60947-2 - Connection pitch : 35 mm
- Local signalling : Positive contact indication
- Long time pick-up adjustment type Ir : Adjustable
- Long time pick-up adjust. range : 0.7 .. 1 x In
- Long time delay adjustment type : Fixed
- [tr] long-time delay adjustment range :
15 s 6 x Ir
120…400 s 1.5 x In - Short-time pick-up adjustment type Isd : Fixed
- [Isd] short-time pick-up adjustment range : 800 A
- Short-time delay adjustment type : Fixed
Environment
- Overvoltage category : Class II
- Electrical shock protection class : Class II
- Standards : EN/IEC 60947
- Product certifications :
CCC
Marine
EAC - IP degree of protection : IP40 conform. to IEC 60529
- IK degree of protection : IK07 conform. to IEC 62262
- Ambient air temperature for operation : -35…70 °C
- Ambient air temperature for storage : -55…85 °C
Schneider Circuit Breaker EZC250F3250 EasyPact
Only logged in customers who have purchased this product may leave a review.
Reviews