Description
Spesifikasi Schneider Contactor LC1D09BD
- Merk : Schneider Electric
- Model / Part Number : LC1D09BD
- Series : TeSys D
Main
- Range : TeSys
- Product name : TeSys D
- Product Type: Contactor
- Short name : LC1D
- Contactor application :
Motor control
Resistive load - Utilisation category :
AC-1
AC-3
AC-4 - Poles : 3P
- Power pole : 3 NO
- [Ue] Rated operational voltage :
<= 300 V DC for power circuit
<= 690 V AC 25…400 Hz for power circuit - Control circuit type : DC standard
- [Uc] control circuit voltage : 24 V DC
- Auxiliary : 1 NO + 1 NC
- Overvoltage Cat : III
- [Ith] Convent. free air therm. curr. :
25 A for power circuit
10 A for signalling circuit - Irms rated making capacity :
250 A for power circuit conform. to IEC 60947
140 A AC for signal. circuit
250 A DC for signal. circuit - Rated breaking : 250 A at 440 V for power circuit conform. to IEC 60947
- Rated short time withstand curr. :
105 A <= 40 °C 10 s power circuit
210 A <= 40 °C 1 s power circuit
30 A <= 40 °C 10 min power circuit
61 A <= 40 °C 1 min power circuit
100 A 1 s signalling circuit
120 A 500 ms signalling circuit
140 A 100 ms signalling circuit - Associated fuse rating :
20 A gG at <= 690 V coordinat. type 2
25 A gG at <= 690 V coordinat. type 1
10 A gG for signal. circuit conform. to IEC 60947-5-1 - Average impedance : 2.5 mOhm at 50 Hz – Ith 25 A for power circuit
- Electrical durability :
0.6 Mcycles 25 A AC-1 at Ue <= 440 V
2 Mcycles 9 A AC-3 at Ue <= 440 V - Power dissipation per pole :
0.2 W AC-3
1.56 W AC-1 - Safety cover : With
- Mounting support :
Rail
Plate - Standards :
CSA C22.2 No 14
EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
UL 508 - Product certifications :
DNV
CSA
GOST
CCC
LROS (Lloyds register of shipping)
GL
UL
BV
RINA - Connections – terminals :
Control circuit : screw clamp terminals 2 cable(s) 1…2.5 mm² – cable stiffness: flexible – with cable end
Power circuit : screw clamp terminals 1 cable(s) 1…4 mm² – cable stiffness: flexible – with cable end
Control circuit : screw clamp terminals 1 cable(s) 1…4 mm² – cable stiffness: flexible – without cable end
Control circuit : screw clamp terminals 2 cable(s) 1…4 mm² – cable stiffness: flexible – without cable end
Control circuit : screw clamp terminals 1 cable(s) 1…4 mm² – cable stiffness: flexible – with cable end
Control circuit : screw clamp terminals 1 cable(s) 1…4 mm² – cable stiffness: solid – without cable end
Control circuit : screw clamp terminals 2 cable(s) 1…4 mm² – cable stiffness: solid – without cable end
Power circuit : screw clamp terminals 1 cable(s) 1…4 mm² – cable stiffness: flexible – without cable end
Power circuit : screw clamp terminals 2 cable(s) 1…4 mm² – cable stiffness: flexible – without cable end
Power circuit : screw clamp terminals 2 cable(s) 1…2.5 mm² – cable stiffness: flexible – with cable end
Power circuit : screw clamp terminals 1 cable(s) 1…4 mm² – cable stiffness: solid – without cable end
Power circuit : screw clamp terminals 2 cable(s) 1…4 mm² – cable stiffness: solid – without cable end - Tightening torque :
Power circuit : 1.7 N.m – on screw clamp terminals – with screwdriver flat Ø 6 mm
Power circuit : 1.7 N.m – on screw clamp terminals – with screwdriver Philips No 2
Control circuit : 1.7 N.m – on screw clamp terminals – with screwdriver flat Ø 6 mm
Control circuit : 1.7 N.m – on screw clamp terminals – with screwdriver Philips No 2 - Operating time :
53.55…72.45 ms closing
16…24 ms opening - Safety reliability level :
B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 - Mechanical durability : 30 Mcycles
- Operating rate : 3600 cyc/h at <= 60 °C
Complementary
- Coil technology : Built-in bidirectional peak limiting diode suppressor
- Control circuit voltage limits :
0.1…0.25 Uc drop-out at 60 °C, DC
0.7…1.25 Uc operational at 60 °C, DC - Time constant : 28 ms
- Inrush power in W : 5.4 W at 20 °C
- Hold-in power consumption in W : 5.4 W at 20 °C
- Auxiliary contacts type :
Type mechanically linked (1 NO + 1 NC) conforming to IEC 60947-5-1
Type mirror contact (1 NC) conforming to IEC 60947-4-1 - Signalling circuit frequency : 25…400 Hz
- Minimum switching current : 5 mA for signalling circuit
- Minimum switching voltage : 17 V for signalling circuit
- Non-overlap time :
1.5 ms on energisation between NC and NO contact
1.5 ms on de-energisation between NC and NO contact
Insulation resistance : > 10 MOhm for signalling circuit
Environment
- IP degree of protection : IP20 front face conforming to IEC 60529
- Protective treatment : TH conforming to IEC 60068-2-30
- Pollution degree : 3
- Ambient air temperature for operation : -5…60 °C
- Ambient air temperature for storage : -60…80 °C
- Permissible ambient air temperature around the device : -40…70 °C at Uc
- Operating altitude : 3000 m without derating
- Fire resistance : 850 °C conforming to IEC 60695-2-1
- Flame retardance : V1 conforming to UL 94
- Mechanical robustness :
Vibrations contactor open 2 Gn, 5…300 Hz
Vibrations contactor closed 4 Gn, 5…300 Hz
Shocks contactor open 10 Gn for 11 ms
Shocks contactor closed 15 Gn for 11 ms
Reviews