Foto Schneider Contactor LC1D25M7

Schneider Contactor LC1D25M7

Jual Schneider Kontaktor model LC1D25M7

Untuk kebutuhan elektrikal di industri dan perumahan merk Schneider Electric Resmi.

Rp0,00

Deskripsi

Spesifikasi Schneider Contactor LC1D25M7

  • Merk : Schneider Electric
  • Model / Part Number : LC1D25M7
  • Series : TeSys D

Main

  • Range : TeSys
  • Product name : TeSys D
  • Product or component type : Contactor
  • Device short name : LC1D
  • Contactor application :
    Motor control
    Resistive load
  • Utilisation category :
    AC-1
    AC-3
    AC-4
  • Poles description : 3P
  • Power pole contact composition : 3 NO
  • [Ue] Rated operational voltage :
    Power circuit: <= 690 V AC 25…400 Hz
    Power circuit: <= 300 V DC
  • [Ie] Rated operational current :
    25 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
    40 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
  • Motor power kW :
    5.5 kW at 220…230 V AC 50/60 Hz (AC-3)
    11 kW at 380…400 V AC 50/60 Hz (AC-3)
    11 kW at 415…440 V AC 50/60 Hz (AC-3)
    15 kW at 500 V AC 50/60 Hz (AC-3)
    15 kW at 660…690 V AC 50/60 Hz (AC-3)
    5.5 kW at 400 V AC 50/60 Hz (AC-4)
  • Motor power HP (UL / CSA) :
    3 hp at 230/240 V AC 50/60 Hz for 1 phase motors
    2 hp at 115 V AC 50/60 Hz for 1 phase motors
    7.5 hp at 230/240 V AC 50/60 Hz for 3 phases motors
    15 hp at 460/480 V AC 50/60 Hz for 3 phases motors
    20 hp at 575/600 V AC 50/60 Hz for 3 phases motors
    7.5 hp at 200/208 V AC 50/60 Hz for 3 phases motors
  • Control circuit type : AC at 50/60 Hz
  • [Uc] Control circuit voltage : 220 V AC 50/60 Hz
  • Auxiliary contact composition : 1 NO + 1 NC
  • [Uimp] Rated impulse withstand voltage : 6 kV conforming to IEC 60947
  • Overvoltage category : III
  • [Ith] Conventional free air thermal current :
    10 A (at 60 °C) for signalling circuit
    40 A (at 60 °C) for power circuit
  • Irms rated making capacity :
    140 A AC for signalling circuit conforming to IEC 60947-5-1
    250 A DC for signalling circuit conforming to IEC 60947-5-1
    450 A at 440 V for power circuit conforming to IEC 60947
  • Rated breaking capacity : 450 A at 440 V for power circuit conforming to IEC 60947
  • [Icw] Rated short-time withstand current :
    240 A 40 °C – 10 s for power circuit
    380 A 40 °C – 1 s for power circuit
    50 A 40 °C – 10 min for power circuit
    120 A 40 °C – 1 min for power circuit
    100 A – 1 s for signalling circuit
    120 A – 500 ms for signalling circuit
    140 A – 100 ms for signalling circuit
  • Associated fuse rating :
    10 A gG for signalling circuit conforming to IEC 60947-5-1
    63 A gG at <= 690 V coordination type 1 for power circuit
    40 A gG at <= 690 V coordination type 2 for power circuit
  • Average impedance : 2 mOhm – Ith 40 A 50 Hz for power circuit
  • [Ui] Rated insulation voltage :
    Power circuit: 690 V conforming to IEC 60947-4-1
    Power circuit: 600 V CSA certified
    Power circuit: 600 V UL certified
    Signalling circuit: 690 V conforming to IEC 60947-1
    Signalling circuit: 600 V CSA certified
    Signalling circuit: 600 V UL certified
  • Electrical durability :
    1.65 Mcycles 25 A AC-3 at Ue <= 440 V
    1.4 Mcycles 40 A AC-1 at Ue <= 440 V
  • Power dissipation per pole :
    3.2 W AC-1
    1.25 W AC-3
  • Safety cover : With
  • Mounting support :
    Plate
    Rail
  • Standards :
    CSA C22.2 No 14
    EN 60947-4-1
    EN 60947-5-1
    IEC 60947-4-1
    IEC 60947-5-1
    UL 508
  • Product certifications :
    BV
    GL
    LROS (Lloyds register of shipping)
    GOST
    UL
    DNV
    CCC
    CSA
    RINA
  • Connections – terminals :
    Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end
    Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end
    Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end
    Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end
    Control circuit: screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end
    Control circuit: screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end
    Power circuit: screw clamp terminals 1 cable(s) 2.5…10 mm²flexible without cable end
    Power circuit: screw clamp terminals 2 cable(s) 2.5…10 mm²flexible without cable end
    Power circuit: screw clamp terminals 1 cable(s) 1…10 mm²flexible with cable end
    Power circuit: screw clamp terminals 2 cable(s) 1.5…6 mm²flexible with cable end
    Power circuit: screw clamp terminals 1 cable(s) 1.5…10 mm²solid without cable end
    Power circuit: screw clamp terminals 2 cable(s) 2.5…10 mm²solid without cable end
  • Tightening torque :
    Control circuit: 1.7 N.m – on screw clamp terminals – with screwdriver flat Ø 6 mm
    Control circuit: 1.7 N.m – on screw clamp terminals – with screwdriver Philips No 2
    Power circuit: 2.5 N.m – on screw clamp terminals – with screwdriver flat Ø 6 mm
    Power circuit: 2.5 N.m – on screw clamp terminals – with screwdriver Philips No 2
  • Operating time :
    12…22 ms closing
    4…19 ms opening
  • Safety reliability level :
    B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
    B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
  • Mechanical durability : 15 Mcycles
  • Maximum operating rate : 3600 cyc/h 60 °C

Complementary

  • Coil technology : Without built-in suppressor module
  • Control circuit voltage limits :
    Drop-out: 0.3…0.6 Uc AC 50/60 Hz (at 60 °C)
    Operational: 0.8…1.1 Uc AC 50 Hz (at 60 °C)
    Operational: 0.85…1.1 Uc AC 60 Hz (at 60 °C)
  • Inrush power in VA :
    70 VA 60 Hz cos phi 0.75 (at 20 °C)
    70 VA 50 Hz cos phi 0.75 (at 20 °C)
  • Hold-in power consumption in VA :
    7.5 VA 60 Hz cos phi 0.3 (at 20 °C)
    7 VA 50 Hz cos phi 0.3 (at 20 °C)
  • Heat dissipation : 2…3 W at 50/60 Hz
  • Auxiliary contacts type :
    type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1
    type mirror contact 1 NC conforming to IEC 60947-4-1
  • Signalling circuit frequency : 25…400 Hz
  • Minimum switching current : 5 mA for signalling circuit
  • Minimum switching voltage : 17 V for signalling circuit
  • Non-overlap time :
    1.5 ms on de-energisation between NC and NO contact
    1.5 ms on energisation between NC and NO contact
  • Insulation resistance : > 10 MOhm for signalling circuit

Environment

  • IP degree of protection : IP20 front face conforming to IEC 60529
  • Protective treatment : TH conforming to IEC 60068-2-30
  • Pollution degree : 3
  • Ambient air temperature for operation : -5…60 °C
  • Ambient air temperature for storage : -60…80 °C
  • Permissible ambient air temperature around the device : -40…70 °C at Uc
  • Operating altitude : 3000 m without
  • Fire resistance : 850 °C conforming to IEC 60695-2-1
  • Flame retardance : V1 conforming to UL 94
  • Mechanical robustness :
    Vibrations contactor open: 2 Gn, 5…300 Hz
    Vibrations contactor closed: 4 Gn, 5…300 Hz
    Shocks contactor closed: 15 Gn for 11 ms
    Shocks contactor open: 8 Gn for 11 ms

Informasi Tambahan

Berat370 g
Dimensi95 × 45 × 85 mm

Datasheet

Ulasan

Belum ada ulasan.

Hanya pelanggan yang sudah login dan telah membeli produk ini yang dapat memberikan ulasan.