Schneider Contactor LP1K0910BD TeSys K

Agen resmi Schneider Magnetic Contactor untuk wilayah Indonesia.

TeSys K Series Contactor – 3P – AC-3 <= 440 V 9 A – 1 NO aux. – 24 V DC coil.

Rp0,00

Description

Spesifikasi Schneider Magnetic Contactor LC1D25M7

  • Merk : Schneider Electric
  • Model / Part Number : LP1K0910BD
  • Series : TeSys K

Main

  • Range of product : TeSys K
  • Range : TeSys
  • Product or component type : Contactor
  • Device short name : LP1K
  • Contactor application :
    Motor control
    Resistive load
  • Utilisation category :
    AC-3
    AC-1
    AC-4
  • Poles description : 3P
  • Pole contact composition : 3 NO
  • [Ie] Rated operational current :
    20 A (at <50 °C) at <= 440 V AC AC-1 for power circuit
    9 A at <= 440 V AC AC-3 for power circuit
    16 A (at <70 °C) at 690 V AC AC-1 for power circuit
  • Auxiliary contact composition : 1 NO

Complementary

  • Auxiliary contacts type : type instantaneous 1 NO
  • Control circuit voltage limits :
    Operational: 0.8…1.15 Uc (at <50 °C)
    Drop-out: 0.1…0.75 Uc (at <50 °C)
  • [Ui] Rated insulation voltage :
    Power circuit: 600 V conforming to UL 508
    Power circuit: 690 V conforming to IEC 60947-4-1
    Signalling circuit: 690 V conforming to IEC 60947-4-1
    Signalling circuit: 690 V conforming to IEC 60947-5-1
    Signalling circuit: 600 V conforming to UL 508
    Power circuit: 600 V conforming to CSA C22.2 No 14
    Signalling circuit: 600 V conforming to CSA C22.2 No 14
  • [Uimp] Rated impulse withstand voltage : 8 kV
  • Overvoltage category : III
  • Mounting support :
    Rail
    Plate
  • Flame retardance :
    V1 conforming to UL 94
    Requirement 2 conforming to NF F 16-101
    Requirement 2 conforming to NF F 16-102
  • Tightening torque :
    1.3 N.m – on screw clamp terminals – with screwdriver Philips No 2
    1.3 N.m – on screw clamp terminals – with screwdriver flat Ø 6 mm
  • [Ue] Rated operational voltage :
    Power circuit: 690 V AC 50/60 Hz
    Signalling circuit: <= 690 V AC 50/60 Hz
  • [Ith] Conventional free air thermal current :
    20 A (at 50 °C) for power circuit
    10 A (at 50 °C) for signalling circuit
  • Irms rated making capacity :
    110 A AC for power circuit conforming to NF C 63-110
    110 A AC for power circuit conforming to IEC 60947
    110 A AC for signalling circuit conforming to IEC 60947
  • Rated breaking capacity :
    110 A at 415 V conforming to IEC 60947
    110 A at 440 V conforming to IEC 60947
    80 A at 500 V conforming to IEC 60947
    110 A at 220…230 V conforming to IEC 60947
    110 A at 380…400 V conforming to IEC 60947
    70 A at 660…690 V conforming to IEC 60947
  • Associated fuse rating :
    25 A gG at <= 440 V for power circuit
    25 A aM for power circuit
    10 A gG for signalling circuit conforming to IEC 60947
    10 A gG for signalling circuit conforming to VDE 0660
  • Average impedance : 3 mOhm – Ith 20 A 50 Hz for power circuit
  • Inrush power in W : 3 W (at 20 °C)
  • Hold-in power consumption in W : 3 W at 20 °C
  • Operating time :
    30…40 ms coil energisation and NO closing
    10 ms coil de-energisation and NO opening
  • Safety reliability level :
    B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
    B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
  • Mechanical durability : 10 Mcycles
  • Maximum operating rate : 3600 cyc/h
  • Minimum switching current : 5 mA for signalling circuit
  • Minimum switching voltage : 17 V for signalling circuit
  • Insulation resistance : > 10 MOhm for signalling circuit

Environment

  • Product certifications :
    UL
    CSA
  • Ambient air temperature for operation : -25…50 °C
  • Ambient air temperature for storage : -50…80 °C
  • Operating altitude : 2000 m without

Video Schneider Contactor LP1K0910BD 

Additional information

Weight225 g
Dimensions57 × 45 × 58 mm

Datasheet

Reviews

There are no reviews yet.

Only logged in customers who have purchased this product may leave a review.