Schneider MCCB model LV426100 16A 3P 16kA at 380/415V(IEC)

Rp0,00

Description

Spesifikasi Schneider MCCB (Molded Case Circuit Breakers) LV426100

  • Merk : Schneider Electric
  • Model / Part Number : LV426100

Main

  • Range : Compact
  • Product name : Compact NSXm
  • Device short name : NSXm 16E
  • Component type : Circuit breaker
  • Device application :
    Protection
    Distribution

Complementary

  • [In] Rated current : 16 A
  • Poles description : 3P 3d
  • Control type : Toggle
  • Mounting mode :
    By screws (plate)
    Clip-on (DIN rail)
  • Network type : AC
  • Network frequency : 50/60 Hz
  • Breaking capacity code : 16 kA 415 V AC
  • [Icu] Rated ultimate breaking capacity :
    Icu 25 kA at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
    Icu 16 kA at 380…415 V AC 50/60 Hz conforming to IEC 60947-2
    Icu 10 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
    Icu 8 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
  • [Ue] Rated operational voltage : 690 V AC 50/60 Hz conforming to IEC 60947-2
  • [Ics] Rated service breaking capacity :
    25 kA at 220…240 V AC 50/60 Hz conforming to IEC 60947-2
    16 kA at 380…415 V AC 50/60 Hz conforming to IEC 60947-2
    10 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
    8 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
  • [Uimp] Rated impulse withstand voltage : 8 kV conforming to IEC 60947-2
  • [Ui] Rated insulation voltage : 800 V conforming to IEC 60947-2
  • Trip unit technology : Thermal-magnetic
  • Trip unit name : TM-D
  • Trip unit protection functions : LI
  • Trip unit rating : 16 A at 40 °C
  • Protection type :
    Short-circuit protection (magnetic)
    Overload protection (thermal)
  • Long time pick-up adjustment range : 0.7…1 x In
  • Short-time pick-up adjustment type Isd : Fixed
  • Short-time delay adjustment type : Fixed
  • Magnetic hold current : 400 A
  • Magnetic tripping current : 600 A
  • Suitability for isolation : Yes conforming to IEC 60947-2
  • Utilisation category : Category A
    9 mm pitches
    9 module
  • Connection pitch :
    35 mm with spreaders
    27 mm without spreaders
  • Connections – terminals :
    1 Everlink lug wire size 2.5…95 mm², rigid or stranded aluminium/copper
    1 Everlink lug wire size 2.5…70 mm², flexible copper
  • Tightening torque :
    5 N.m for 2.5…10 mm²
    9 N.m for 16…95 mm²
  • Local signalling : Presence of auxiliary contacts: flag (green)
  • Number of slots :
    1 slot(s) for auxiliary switch OF
    1 slot(s) for alarm switch SD
    1 slot(s) for voltage release MN or MX
  • Power wire stripping length : 20 mm

Environment

  • Quality labels : CE
  • Standards : EN/IEC 60947
  • Product certifications :
    CCC
    EAC
    Marine
  • Colour : Grey (RAL 7016)
  • IP degree of protection : Front cover: IP40 conforming to IEC 60529
  • IK degree of protection : IK07 conforming to IEC 62262
  • Pollution degree : 3 conforming to IEC 60947-1
  • Ambient air temperature for operation : -25…70 °C
  • Ambient air temperature for storage : -40…85 °C
  • Operating altitude :
    2000 m without derating
    5000 m with derating
  • Mechanical durability : 20000 cycles conforming to IEC 947-1 Annex K ed 5.2 In
  • Electrical durability : 10000 cycles conforming to IEC 947-1 Annex F ed 5.2 for In at 440 V

Additional information

Weight1060 g
Dimensions80 × 81 × 137 mm