Foto Schneider MCCB LV426101

Schneider MCCB Circuit Breaker LV426101

Jual MCCB Schneider LV426101

Compact NSXm E (16 kA at 415 VAC), 3P, 25 A rating TMD trip unit, EverLink connectors

Rp0,00

Description

Spesifikasi Schneider MCCB (Molded Case Circuit Breakers) LV426101

  • Merk : Schneider Electric
  • Model / Part Number : LV426101
  • Series : Compact NSXm

Main

  • Short name : NSXm 25E
  • Product or component type : Circuit breaker
  • Device application :
    Protection
    Distribution

Complementary

  • [In] rated current : 25 A
  • Poles description : 3P 3d
  • Control type : Toggle
  • Mounting mode :
    By screws for plate
    Clip-on for DIN rail
  • Network type : AC
  • Network frequency : 50/60 Hz
  • Breaking capacity code : E 16 kA 415 V AC
  • [Icu] Rated ultimate breaking capacity :
    25 kA at 220…240 V AC 50/60 Hz according to IEC 60947-2
    16 kA at 380…415 V AC 50/60 Hz according to IEC 60947-2
    10 kA at 440 V AC 50/60 Hz according to IEC 60947-2
    8 kA at 500 V AC 50/60 Hz according to IEC 60947-2
  • [Ue] Rated operational voltage : 690 V AC 50/60 Hz according to IEC 60947-2
  • [Ics] Rated service breaking capacity :
    25 kA at 220…240 V AC 50/60 Hz according to IEC 60947-2
    16 kA at 380…415 V AC 50/60 Hz according to IEC 60947-2
    10 kA at 440 V AC 50/60 Hz according to IEC 60947-2
    8 kA at 500 V AC 50/60 Hz according to IEC 60947-2
  • [Uimp] Rated impulse withstand voltage : 8 kV according to IEC 60947-2
  • [Ui] Rated insulation voltage : 800 V according to IEC 60947-2
  • Trip unit technology : Thermal-magnetic
  • Trip unit name : TM-D
  • Trip unit protection functions : LI
  • Trip unit rating : 25 A at 40 °C
  • Protection type :
    Overload protection (thermal)
    Short-circuit protection (magnetic)
  • Long time pick-up adjustment range : 0.7…1 x In
  • Short-time pick-up adjustment type Isd : Fixed
  • Short-time delay adjustment type : Fixed
  • Magnetic hold current : 480 A
  • Magnetic tripping current : 720 A
  • Suitability for isolation : Yes according to IEC 60947-2
  • Utilisation category : Category A
  • 9 mm pitches : 9 module
  • Connection pitch :
    35 mm with spreaders
    27 mm without spreaders
  • Connections – terminals :
    1 Everlink lug 2.5…70 mm² (flexible) conductor :copper
    1 Everlink lug 2.5…95 mm² (rigid or stranded) conductor :aluminium/copper
  • Tightening torque :
    5 N.m for 2.5…10 mm²
    9 N.m for 16…95 mm²
  • Local signalling : Green flag for presence of auxiliary contacts
  • Number of slots :
    1 slot(s) for auxiliary switch OF
    1 slot(s) for alarm switch SD
    1 slot(s) for voltage release MN or MX
  • Power wire stripping length : 20 mm

Environment

  • Quality labels : CE
  • Standards : EN/IEC 60947
  • Product certifications :
    CCC
    EAC
    Marine
  • Colour : Grey (RAL 7016)
  • IP degree of protection : IP40 (front cover) according to IEC 60529
  • IK degree of protection : IK07 according to IEC 62262
  • Pollution degree : 3 according to IEC 60947-1
  • Ambient air temperature for operation : -25…70 °C
  • Ambient air temperature for storage : -40…85 °C
  • Operating altitude :
    5000 m with derating
    2000 m without derating
  • Mechanical durability : 20000 cycles according to IEC 947-1 Annex K ed 5.2 for In
  • Electrical durability : 10000 cycles according to IEC 947-1 Annex F ed 5.2 for In at 440 V

Additional information

Weight1060 g
Dimensions80 × 81 × 137 mm

Datasheet

Reviews

There are no reviews yet.

Only logged in customers who have purchased this product may leave a review.